From the field
Field Notes
These are representative cases built from fault patterns that are common in the field. Each one follows a single fault from start to finish: what the alarm said, what was measured, which possibilities were ruled out, what the root cause was and how it was closed. No specific wind farm, turbine or date is described; numbers are examples. The aim is the diagnostic sequence, not the result.
A fault tree gives you a fast route from symptom to cause; these pages show you what it is like inside one case. The two complement each other: narrow it down with the tree first, then read the closest case here.
Note: these are field experience, not a substitute for the manufacturer's service documentation. Your own turbine's OEM instructions, LOTO procedure and site safety rules govern every intervention.
Case database
Representative cases, filterable
- Cases
- 7
- Systems
- 5
- Fault types
- 3
- Caught by
- 3
System
Fault type
How it was caught
7 cases shown
- System
- Pitch
- Fault type
- Mechanical
- How it was caught
- Alarm
- Component
- Pitch gearbox
SymptomA “pitch motor current high” alarm on one axis; the pitch system is not ready at morning start-up.
Root causeA slow oil leak at the output shaft seal; the gearbox ran short of oil for months and wore.
Show the diagnostic path
- Symptom
A “pitch motor current high” alarm on one axis; the pitch system is not ready at morning start-up.
- Measurement
Axes moved one by one in service mode: one axis is stiff. Winding balanced, motor brake releases fully.
- Root cause
A slow oil leak at the output shaft seal; the gearbox ran short of oil for months and wore.
- Fix
Gearbox replaced to the OEM procedure; the other two gearboxes checked for level and leaks.
- Lesson
Watch the slope, not the threshold: the current rise was visible in the SCADA trend months earlier.
Case 02Representative
Gearbox temperature rises with wind
60–65 → 78–82 °CExample · neighbours → this turbine
- System
- Gearbox
- Fault type
- Mechanical
- How it was caught
- SCADA warning
- Component
- Shaft seal · oil level
SymptomGearbox temperature warning for three windy days; the turbine keeps running.
Root causeA leaking shaft seal; with the level low, less oil passed through the cooler.
Show the diagnostic path
- Symptom
Gearbox temperature warning for three windy days; the turbine keeps running.
- Measurement
On a temperature-versus-power plot the turbine sits in its own band above its neighbours. Oil level below minimum, oily dust around the breather.
- Root cause
A leaking shaft seal; with the level low, less oil passed through the cooler.
- Fix
Oil topped up with the OEM-approved type, leak monitored; seal replacement and oil analysis scheduled.
- Lesson
Read temperature against power, and next to the neighbours — not against time.
Case 03Representative
Yaw hunting: the nacelle swings back and forth
Yaw count ×3Example · versus neighbours
- System
- Yaw
- Fault type
- Sensor · Mechanical
- How it was caught
- SCADA warning
- Component
- Wind vane · yaw brake
SymptomIn gusty wind the nacelle keeps reversing; rhythmic knocking, hourly yaw count far above neighbours.
Root causeA loose wind vane, weak brake holding and late bearing lubrication — together.
Show the diagnostic path
- Symptom
In gusty wind the nacelle keeps reversing; rhythmic knocking, hourly yaw count far above neighbours.
- Measurement
Wind direction signal offset and noisy compared with neighbours; yaw brake residual pressure below its lower limit.
- Root cause
A loose wind vane, weak brake holding and late bearing lubrication — together.
- Fix
Vane tightened and realigned, brake leak fixed and pressure set, bearing lubricated.
- Lesson
Hunting rarely has a single cause; check sensors and mechanics before suspecting parameters.
Case 04Representative
Generator temperature alarm: sensor or real heat?
+15–20 °CExample · one channel, constant offset
- System
- Generator
- Fault type
- Sensor
- How it was caught
- Alarm
- Component
- PT100 terminal
SymptomAt high power one winding channel crosses the threshold and the turbine stops; after reset the alarm returns.
Root causeAn oxidised, loose terminal connection adding resistance and pushing the reading up.
Show the diagnostic path
- Symptom
At high power one winding channel crosses the threshold and the turbine stops; after reset the alarm returns.
- Measurement
The same channel still reads high on a cooled machine. Resistance correct at the sensor, a few ohms higher at the controller input.
- Root cause
An oxidised, loose terminal connection adding resistance and pushing the reading up.
- Fix
Terminal renewed and tightened; the channel returned to the band of the others. The alarm limit was not changed.
- Lesson
Never raise the alarm limit or bypass a channel; verify the measuring chain first.
Case 05Representative
Converter overcurrent only at high power
17 / 19 eventsExample · near rated power
- System
- Converter
- Fault type
- Electrical
- How it was caught
- Alarm
- Component
- DC busbar joint
SymptomIntermittent converter overcurrent trips; every check on the stopped turbine is clean.
Root causeA DC busbar joint that had lost its torque, heating at high current and stressing the neighbouring module.
Show the diagnostic path
- Symptom
Intermittent converter overcurrent trips; every check on the stopped turbine is clean.
- Measurement
Events matched high power. A thermal scan done with an OEM-approved method showed a hot DC busbar joint.
- Root cause
A DC busbar joint that had lost its torque, heating at high current and stressing the neighbouring module.
- Fix
After LOTO, discharge and a verified zero-voltage test, the joint was renewed and torqued to OEM value; the stressed module was replaced.
- Lesson
With intermittent faults, look for the condition that triggers them — not the fault message.
Case 06Representative
Yaw bearing wear: metal in the purged grease
No alarmCaught during routine greasing
- System
- Yaw
- Fault type
- Mechanical
- How it was caught
- Field observation
- Component
- Yaw lubrication line
SymptomThe turbine is producing. Dark, metallic grease from some purge points; a rubbing noise at one nacelle position.
Root causeA blocked lubrication line left one sector of the bearing without grease.
Show the diagnostic path
- Symptom
The turbine is producing. Dark, metallic grease from some purge points; a rubbing noise at one nacelle position.
- Measurement
Grease collected point by point; metal concentrated at three neighbouring points, a magnet test confirmed steel particles.
- Root cause
A blocked lubrication line left one sector of the bearing without grease.
- Fix
Line cleared, distributor replaced, sector greased; close follow-up at short intervals.
- Lesson
A running pump does not mean grease reaches every point.
- System
- Pitch
- Fault type
- Sensor
- How it was caught
- Field observation
- Component
- Pitch angle reference
SymptomNacelle vibration only in one wind band; no visible blade damage.
Root causeAfter an earlier encoder replacement the blade angle reference had not been calibrated correctly.
Show the diagnostic path
- Symptom
Nacelle vibration only in one wind band; no visible blade damage.
- Measurement
Spectrum dominated by 1P with normal 3P; a physical measurement found one blade at a different angle.
- Root cause
After an earlier encoder replacement the blade angle reference had not been calibrated correctly.
- Fix
All three blade angle references reset to the physical marks with the OEM method; 1P dropped.
- Lesson
Look at the spectrum before calling a blade inspection.
No case matches these filters.
Remove one of the filters, or try the diagnosis simulator.
The cases are representative: built from common field patterns, values are examples. OEM and model names are deliberately not given.
Frequently asked
What should you do first when a turbine faults?
Before you read the alarm, make it safe: stop the turbine, apply LOTO, isolate the system you are going to touch. Then pull the OEM fault log and the SCADA trend. The trend tells you far more than a single instantaneous reading: did this start today, or has it been growing for weeks?
Why does a SCADA value differ from what you measure on site?
Usually the measuring chain: a loose or oxidised terminal, a damaged cable or a drifting sensor. On a temperature alarm, first compare with the other channels on the same machine; on a stopped, cooled machine all channels should read close to each other. Measuring the surface with an infrared thermometer is not proof on its own, because the inside of a winding is hotter than the housing.