Soner Soylu

From the field

Field Notes

These are representative cases built from fault patterns that are common in the field. Each one follows a single fault from start to finish: what the alarm said, what was measured, which possibilities were ruled out, what the root cause was and how it was closed. No specific wind farm, turbine or date is described; numbers are examples. The aim is the diagnostic sequence, not the result.

A fault tree gives you a fast route from symptom to cause; these pages show you what it is like inside one case. The two complement each other: narrow it down with the tree first, then read the closest case here.

Note: these are field experience, not a substitute for the manufacturer's service documentation. Your own turbine's OEM instructions, LOTO procedure and site safety rules govern every intervention.

Case database

Representative cases, filterable

Cases
7
Systems
5
Fault types
3
Caught by
3

System

Fault type

How it was caught

7 cases shown

Case 01Representative

Pitch motor draws high current

12 A → 18 AExample value · one axis

System
Pitch
Fault type
Mechanical
How it was caught
Alarm
Component
Pitch gearbox

SymptomA “pitch motor current high” alarm on one axis; the pitch system is not ready at morning start-up.

Root causeA slow oil leak at the output shaft seal; the gearbox ran short of oil for months and wore.

Show the diagnostic path
  1. Symptom

    A “pitch motor current high” alarm on one axis; the pitch system is not ready at morning start-up.

  2. Measurement

    Axes moved one by one in service mode: one axis is stiff. Winding balanced, motor brake releases fully.

  3. Root cause

    A slow oil leak at the output shaft seal; the gearbox ran short of oil for months and wore.

  4. Fix

    Gearbox replaced to the OEM procedure; the other two gearboxes checked for level and leaks.

  5. Lesson

    Watch the slope, not the threshold: the current rise was visible in the SCADA trend months earlier.

Full case

Case 02Representative

Gearbox temperature rises with wind

60–65 → 78–82 °CExample · neighbours → this turbine

System
Gearbox
Fault type
Mechanical
How it was caught
SCADA warning
Component
Shaft seal · oil level

SymptomGearbox temperature warning for three windy days; the turbine keeps running.

Root causeA leaking shaft seal; with the level low, less oil passed through the cooler.

Show the diagnostic path
  1. Symptom

    Gearbox temperature warning for three windy days; the turbine keeps running.

  2. Measurement

    On a temperature-versus-power plot the turbine sits in its own band above its neighbours. Oil level below minimum, oily dust around the breather.

  3. Root cause

    A leaking shaft seal; with the level low, less oil passed through the cooler.

  4. Fix

    Oil topped up with the OEM-approved type, leak monitored; seal replacement and oil analysis scheduled.

  5. Lesson

    Read temperature against power, and next to the neighbours — not against time.

Full case

Case 03Representative

Yaw hunting: the nacelle swings back and forth

Yaw count ×3Example · versus neighbours

System
Yaw
Fault type
Sensor · Mechanical
How it was caught
SCADA warning
Component
Wind vane · yaw brake

SymptomIn gusty wind the nacelle keeps reversing; rhythmic knocking, hourly yaw count far above neighbours.

Root causeA loose wind vane, weak brake holding and late bearing lubrication — together.

Show the diagnostic path
  1. Symptom

    In gusty wind the nacelle keeps reversing; rhythmic knocking, hourly yaw count far above neighbours.

  2. Measurement

    Wind direction signal offset and noisy compared with neighbours; yaw brake residual pressure below its lower limit.

  3. Root cause

    A loose wind vane, weak brake holding and late bearing lubrication — together.

  4. Fix

    Vane tightened and realigned, brake leak fixed and pressure set, bearing lubricated.

  5. Lesson

    Hunting rarely has a single cause; check sensors and mechanics before suspecting parameters.

Full case

Case 04Representative

Generator temperature alarm: sensor or real heat?

+15–20 °CExample · one channel, constant offset

System
Generator
Fault type
Sensor
How it was caught
Alarm
Component
PT100 terminal

SymptomAt high power one winding channel crosses the threshold and the turbine stops; after reset the alarm returns.

Root causeAn oxidised, loose terminal connection adding resistance and pushing the reading up.

Show the diagnostic path
  1. Symptom

    At high power one winding channel crosses the threshold and the turbine stops; after reset the alarm returns.

  2. Measurement

    The same channel still reads high on a cooled machine. Resistance correct at the sensor, a few ohms higher at the controller input.

  3. Root cause

    An oxidised, loose terminal connection adding resistance and pushing the reading up.

  4. Fix

    Terminal renewed and tightened; the channel returned to the band of the others. The alarm limit was not changed.

  5. Lesson

    Never raise the alarm limit or bypass a channel; verify the measuring chain first.

Full case

Case 05Representative

Converter overcurrent only at high power

17 / 19 eventsExample · near rated power

System
Converter
Fault type
Electrical
How it was caught
Alarm
Component
DC busbar joint

SymptomIntermittent converter overcurrent trips; every check on the stopped turbine is clean.

Root causeA DC busbar joint that had lost its torque, heating at high current and stressing the neighbouring module.

Show the diagnostic path
  1. Symptom

    Intermittent converter overcurrent trips; every check on the stopped turbine is clean.

  2. Measurement

    Events matched high power. A thermal scan done with an OEM-approved method showed a hot DC busbar joint.

  3. Root cause

    A DC busbar joint that had lost its torque, heating at high current and stressing the neighbouring module.

  4. Fix

    After LOTO, discharge and a verified zero-voltage test, the joint was renewed and torqued to OEM value; the stressed module was replaced.

  5. Lesson

    With intermittent faults, look for the condition that triggers them — not the fault message.

Full case

Case 06Representative

Yaw bearing wear: metal in the purged grease

No alarmCaught during routine greasing

System
Yaw
Fault type
Mechanical
How it was caught
Field observation
Component
Yaw lubrication line

SymptomThe turbine is producing. Dark, metallic grease from some purge points; a rubbing noise at one nacelle position.

Root causeA blocked lubrication line left one sector of the bearing without grease.

Show the diagnostic path
  1. Symptom

    The turbine is producing. Dark, metallic grease from some purge points; a rubbing noise at one nacelle position.

  2. Measurement

    Grease collected point by point; metal concentrated at three neighbouring points, a magnet test confirmed steel particles.

  3. Root cause

    A blocked lubrication line left one sector of the bearing without grease.

  4. Fix

    Line cleared, distributor replaced, sector greased; close follow-up at short intervals.

  5. Lesson

    A running pump does not mean grease reaches every point.

Full case

Case 07Representative

Blade vibration: 1P or 3P?

1P · ~2.5°Example · angle difference

System
Pitch
Fault type
Sensor
How it was caught
Field observation
Component
Pitch angle reference

SymptomNacelle vibration only in one wind band; no visible blade damage.

Root causeAfter an earlier encoder replacement the blade angle reference had not been calibrated correctly.

Show the diagnostic path
  1. Symptom

    Nacelle vibration only in one wind band; no visible blade damage.

  2. Measurement

    Spectrum dominated by 1P with normal 3P; a physical measurement found one blade at a different angle.

  3. Root cause

    After an earlier encoder replacement the blade angle reference had not been calibrated correctly.

  4. Fix

    All three blade angle references reset to the physical marks with the OEM method; 1P dropped.

  5. Lesson

    Look at the spectrum before calling a blade inspection.

Full case

The cases are representative: built from common field patterns, values are examples. OEM and model names are deliberately not given.

Frequently asked

What should you do first when a turbine faults?

Before you read the alarm, make it safe: stop the turbine, apply LOTO, isolate the system you are going to touch. Then pull the OEM fault log and the SCADA trend. The trend tells you far more than a single instantaneous reading: did this start today, or has it been growing for weeks?

Why does a SCADA value differ from what you measure on site?

Usually the measuring chain: a loose or oxidised terminal, a damaged cable or a drifting sensor. On a temperature alarm, first compare with the other channels on the same machine; on a stopped, cooled machine all channels should read close to each other. Measuring the surface with an infrared thermometer is not proof on its own, because the inside of a winding is hotter than the housing.